e. The next question will be what row/s for the high voltage winding will be
tested. If the transformer has no taps or the taps are defined as DETC, then
the software will only allow Selected Row.
f. The next question will be what row/s for the low voltage winding will be
tested. If the transformer has taps and the taps are defined as OLTC, then
the software will allow Selected Row (default), All Rows or Row Range
(partial testing). Once the winding and rows have been defined, press the
Test button to continue.