Transformer Testing
AVTMTO3XX Rev 3 Sept 2013
41
Manual Mode Operation
At the bottom of the form is a separate table for manual mode operation. It may
be required to perform testing that is not typical for a normal test sequence or to
double check a measurement discrepancy generated in the normal test sequence.
This manual mode operation creates the ability to test just use single or dual
winding measurements with fixed output terminals and virtually unlimited
connection opportunities.
Show Manual Tests – Check Button to turn off/on the manual test table.
Right clicking on Test # will start a test with current flowing out H1, H2 and
X1 jumpered in the unit and Current return X2.
Right clicking on the H1-H2 open cell will test resistance using H1-H2 leads.
Right clicking on the X1-X2 open cell will test resistance using X1-X2 leads.
Description, field is used to type any comments the customer wants to
describe the test.