EasyManuals Logo
Home>Megmeet>Thermostat>MTC-08-NT

Megmeet MTC-08-NT User Manual

Default Icon
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
10
MTC-08-NT buffer (BFM) set the control function of the content to table1-9.
Table 1-9 MTC-08-NT buffer (BFM) the control function of the set
BFM
Content
Remarks
Nat
ure
Sa
ve
CH1/CH5
CH2/CH6
CH3/CH7
CH4/CH8
#901/#905
#902/#906
#903/#907
#904/#908
Input type *1
Default value0
R/W
Y
#909/#913
#910/#914
#911/#915
#912/#916
Set value (SV) * 2
Default value0.0
Unit0.1/
R/W
Y
#917/#921
#918/#922
#919/#923
#920/#924
Control output cycle
set * 3
Default value2
Range1100
R/W
Y
#925/#929
#926/#930
#927/#931
#928/#932
Heat side
proportional band
Default value30
Unit0.1
Range0.1%~
1000.0
R/W
Y
#933/#937
#934/#938
#935/#939
#936/#940
Heat side integrativ
e time
Default value240
Range13600
Seconds
R/W
Y
#941/#945
#942/#946
#943/#947
#944/#948
Heat side
derivative
time
Default value60
Range03600
Seconds
R/W
Y
#957/#961
#958/#962
#959/#963
#960/#964
Cool side
proportional band
Default value30
Unit0.1
Range0.1%~
1000.0
R/W
Y
#965/#969
#966/#970
#967/#971
#968/#972
Cool side integrativ
e time
Default value240
Range13600
Seconds
R/W
Y
#973/#977
#974/#978
#975/#979
#976/#980
Cool side
Derivative
time
Default value60
Range03600
Seconds
R/W
Y
#981/#985
#982/#986
#983/#987
#984/#988
Overlap/Deadband*
4
Default value0
No overlapped
non-inductive belt
Setting range:-input
range~+input range
R/W
Y
#989/#993
#990/#994
#991/#995
#992/#996
Undershoot
suppression
factor*5
Water-cooled default
Air-cooled default
Range:0~1000
R/W
Y
#997
Control start/stop
setting of CH1- CH4
*6
Default valueB0000
0Stop 1Start
R/W
Y
#998
Control start/stop
setting of CH5- CH8
*6
Default valueB0000
0Stop 1Start
R/W
Y
M0/M4
M1/M5
M2/M6
M3/M7
Control start/stop
setting of CH1- CH8
*6
Default valueB0000
0Stop 1Start
R/W
Y
#999
Auto-tuning setting
of CH1- CH8 *7
Default valueB0000
0:Not self-tuning or aut
o-tuning has been
completed
1Auto-Tune
R/W
Y