6 7 LCP9H 70 en Liwa
APPROVALS
Intrinsically safe
IECEx Ex ia IIC T6...T4 Gb
Ex ic IIC T6...T4 Gc
Ex eb mb [ib] IIC T6...T4 Gb
IEC 60079-0: 2011
IEC 60079-11: 2011
IEC 60079-18: 2014
IEC 60079-7: 2015
ATEX II 2G Ex ia IIC T6...T4 Gb
II 3G Ex ic IIC T6...T4 Gc
II 2G Ex eb mb [ib] IIC T6...T4 Gb
EN 60079-0: 2012,
EN 60079-7: 2015,
EN 60079-11: 2012,
EN 60079-18: 2015
INMETRO
Ex ia IIC T6...T4 Gb
Ex ic IIC T6...T4 Gc
ABNT NBR IEC 60079-0:2013
ABNT NBR IEC 60079-11:2009
Flameproof and explosion proof
IECEx Ex d IIB+H
2
T6 Gb
Ex tb IIIC T85 °C Db IP66
IEC 60079-0: 2007,
IEC 60079-1: 2007,
IEC 60079-31: 2008
ATEX II 2GD
Ex d IIB + H2 T6 Gb
Ex tb IIIC T85°C Db IP66
EN 60079-0: 2009-10,
EN 60079-1: 2007-04,
EN 60079-31: 2009
INMETRO
Ex d IIB+H2 T6 Gb
Ex tb IIIC T85 °C Db IP65
ABNT NBR IEC 60079-0:2008 versão
corrigida 2011
ABNT NBR IEC 60079-1:2009 versão
corrigida 2011
ABNT NBR IEC 60079-31:2011
ABNT NBR IEC 60529:2009
Electromagnetic protection
Electromagnetic compatibility
Emission acc. to EN 61000-6-4: 2007
Immunity acc. to EN 61000-6-2: 2005
1.6 Recycling and disposal
Most local control panel parts can be recycled if sorted
according to material. Most parts have material marking. In
addition, separate recycling and disposal instructions are
available from the manufacturer.
The Local Control Panel may also be returned to the manufac-
turer for recycling and disposal. There will be a charge for this.
1.7 Safety precautions
2 TRANSPORTATION, RECEPTION AND
STORAGE
The Local Control Panel is a sophisticated instrument, han-
dle it with care.
Check the Local Control Panel for any damage that
may have occurred during transportation.
Store the Local Control Panel preferably indoors and
keep it away from rain and dust.
CAUTION:
Do not exceed the permitted values!
Exceeding the permitted values may cause damage to
the local control panel and to equipment attached to
the panel.
Damage to the equipment and personal injury may
result.
CAUTION:
During maintenance or commissioning when the
device cover is open, ensure that water does not go
inside the enclosure.
CAUTION:
Do not operate the device with the cover open or
removed!
Electromagnetic immunity is reduced.
Ex d WARNING:
Do not open the cover when an explosive atmosphere
may be present!
Ex d and Ex tb WARNING:
Use a cable gland with suitable Ex d IIC and Ex tb IIIC
certification. Use cable gland suitable for at least
-20 °C to 70 °C.
Ex d NOTE:
Only persons familiar with Ex d explosion protection are
allowed to work with the device. Special attention has to
be paid to careful handling and closing of the cover.
NOTE:
Avoid earthing a welding machine in close proximity to
the LCP9H.
Damage to the equipment may result.