STRATA2
5.7.2 connecting of system safety interlocks
These switches are connected to the ‘dark green’ 3 pole plug. The central pole provides the common
output (230V AC). The left hand terminal enables the lower module and the right hand terminal enables
the upper module.
5.7.3 connecting remote run indication lamps
Connection points have been provided for the connection of run indication lamps (20W max). See
“Electrical Connection Details” fig 5.7a, for terminal positions.
CAUTION: These outputs must not be linked together as this will result in false lockout being
experienced by the burner control panels.
Legend
PPS. Connection for the Master boiler to a second boiler -
Note screened cable must be used
.
LPB. Connection for the Master RVA 47 controller to subsequent
RVA 47 controllers -
Note screened cable must be used
.
VFO. Connection for the system flow sensor.
SF. Connection for the DHW sensor.
AF. Connection for the outside air sensor.
RE. Connection for the room unit.
HI. Connection for remote enabling volt free or 0-10 Volt control signal.
RFO. Connection for the system return sensor.
SLP. Connection for the DHW 3 way valve or charging pump. (Max 2A).
HKP. Connection for the Heating pump. (Max 2A).
AF1/AF2. Connection for another outside air sensor dedicated for the RVA 46 if required.
If a dedicated sensor is not required the RVA 46 will use the RVA 47 outside air sensor.
RE1/RE2. Connection for the room unit/thermostat dedicated to the RVA 46 VT circuits
VF1/VF2. Connection for the mixed flow sensor of the RVA 46 VT circuits
P1/P2. Connection for the pump of the RVA 46 VT circuits.
M1/M2. Connection for the 3 way mixing valve of the RVA 46 VT circuits.