on generator power due to high altitude or engine performance problems. Follow the steps in the
“Verifying power to EasyStart” section.
Wrong line voltage
The 120V-only RV EasyStart (-X20-IP) cannot be used in 220V applications.
No signal from start winding
The most common causes of this problem is:
• The orange wire is not connected to the start winding.
• The Compressor Start winding is open.
• Line L2 is connected directly to the compressor start winding.
Testing for a no signal problem:
Turn all power off. Verify there is continuity from the black wire to the orange wire at the wire
connection points. This connection will give only the very low resistance of the common to start winding
connection when it is properly connected. The flow of this path is down the orange EasyStart wire to the
run capacitor. Through the capacitor terminal to the start winding. Through the start winding wire to the
start winding. Out the compressor common terminal and through the overload. Out the overload and
through the compressor common wire. The compressor common wire should be joined with the
EasyStart black wire which completes the path. Any break in this path indicates a problem and will cause
a fault. Correct the open in this path to fix this fault.