PROGRAMMING THE JADE W7220
CONTROLLER
The next several pages detail the di󰀨erent status displays,
setpoints, setup, and alarms available on the controller. This list
below and Table 10 summarizes the inputs required for a standard
application with a single outside air sensor. NOTE: instead of
setting the SETPOINTS you can use the defaults already set in
the Jade controller see default settings below. See Table 10 for
summerized standard settings or for more detail see Table 11 –
Menu Structure.
SETPOINTS
MAT SET: this sets the mixed air temperature (MAT) setting.
The controller has a default of 53 degrees, but the range is
anywhere from 38 to 70 degrees F.
LOW T LOCK: This setting locks out the compressor (or
mechanical cooling) at a given temperature. The default is 32
degrees F, but the controller’s range is from -45 to 80 degrees
F.
DRYBULB SET: if you have an economizer with a dry bulb
outside air sensor you will see and set the DRYBULB SET. The
default setting is 63 degrees F but the controller’s range is 48
to 80 degrees F.
ENTH CURVE: if you have a single enthalpy outside air sensor
instead of a dry bulb, you will see and set the ENTH CURVE
setting. There are 5 setting options: ES1 thru ES5. Check the
economizer literature for the limits for each of these settings.
ES3 is the default setting.
SYSTEM SETUP
INSTALL: Allows you to set the current date. Use the keypad
buttons to scroll to the correct date.
EQUIPMENT: Always set to CONV even if the unit is a heat
pump.
AUX2 IN: Always set to W1.
FAN TYPE: Set for either single or 2 speed. The default is 2
speed.
AUX1 OUT: If remote Fault Detection and Diagnostic (FDD)
monitoring is required select SYS.
OCC: occupancy, always set to INPUT
MIN POS: The minimum position allows for ventilation even
when not in the free-cooling mode. If you have a single speed
unit there will be only one minimum position setting. The
default is 2.8 volts, but the range is 2-10Vdc.
o MIN POS H and MIN POS L: If your unit is 2 speed, there
will be 2 minimum position settings that show up on the menu.
The rst is MIN POS H (for high speed) which has a default of
2.8 volts. The second is MIN POS L (for low speed), which has
a default of 3.2. Note that MIN POS H and MIN POS L are only
displayed if under SYSTEM SETUP: AUX2 IN is set to “W1”,
and FAN TYPE is set to 2 speed.
FOR SINGLE SPEED UNIT FOR 2 SPEED UNITS
Controller Menu
Item
Default Set To: Default Set To: Note
SETPOINTS
MAT SET 53°F 38° to 70°F 53°F 38° to 70°F
LOW T LOCK 32°F -45° to 80°F 32°F -45° to 80°F
DRYBLB SET 63°F 48° to 80°F 63°F 48° to 80°F Only displayed if using single DB OA sensor
ENTH CURVE ES3 ES1 to ES5 ES3 ES1 to ES5 Only displayed if using a single enthalpy OA sensor
MIN POS 2.8 Vdc 2 to 10 Vdc NA Only displayed if set up for single speed unit
MIN POS H NA NA 2.8 Vdc 2 to 10 Vdc Only displayed if set up for 2 speed unit
MIN POS L NA NA 3.2 Vdc 2 to 10 Vdc Only displayed if set up for 2 speed unit
SYSTEM SETUP
INSTALL 1/1/2010 Current date 1/1/2010 Current date
EQUIPMENT CONV CONV CONV CONV Always set to CONV, even on HP units
AUX2 I W1* W1 W1* W1 Always set to W1
FAN TYPE 2 speed* 1 speed 2 speed* 2 speed Default may vary on some models
AUX1 OUT NONE SYS NONE SYS Set to SYS for remote FDD monitoring
OCC INPUT INPUT INPUT INPUT Always set to INPUT
Table 10 - Standard Jade W7220 Controller Conguration
Note 1: For 2 speed unit, under SYSTEM SETUP: EQUIPMENT= CONV, AUX2 I = W1, and FAN TYPE = 2 SPEED
Note 2: More sophisticated controller setups, including for DCV or power exhaust, are available by referring to Table 11 options
NA = Not applicable
*Available on Firmware 1.15 June 2018 and later