Table 11 Menu Structure (cont)*
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
Notes
CHECKOUT
DAMPER VMIN .HS n/a n/a Positions OA damper to VMIN High Speed position
DAMPER VMAX .HS n/a n/a Positions OA damper to VMAX High Speed position
DAMPER OPEN n/a n/a Positions OA damper to the full open position.
DAMPER CLOSE n/a n/a Positions damper to the fully closed position
CONNECT Y1---O n/a n/a Closes the Y1---O relay (Y1---O)
CONNECT Y2---O n/a n/a Closes the Y2---O relay (Y2---O)
CONNECT AUX1O n/a n/a Energizes the AUX1O output. If Aux setting is:
NONE --- not action taken
ERV --- 24 Vac out. Turns on or signals an ERV that the
conditions are not good for economizing but are good for ERV
operation.
d
SYS ‒ 24 Vac out. Issues a system alarm
ALARMS(_)
Alarms display only when they are active. The menu title “ALARMS(_)”
includes the number of active alarms in parenthesis ( ).
MA T SENS ERR n/a n/a MIXED AIR TEMPERATURE SENSOR ERROR
CO2 SENS ERR
n/a n/a
CO2 SENSOR ERROR
OA T SENS ERR
n/a n/a
OUTSIDE AIR TEMPERATURE SENSOR ERROR
OAT sensor connected at input terminals OAT
OA SYLK SENS ERR
n/a n/a
OUTSIDE AIR ENTHALPY SENSOR ERROR
OAT sensor connected on S‒ bus
DA T SENS ERR
n/a n/a
DISCHARGE AIR TEMPERATURE SENSOR ERROR
SYS ALARM
n/a n/a
When AUX1-0 is set to SYS and there is any alarm (e.g., failed
sensors, etc.), the AUX1-0 terminal provides 24 Vac out.
ACT UNDER V
n/a n/a
ACTUATOR VOLTAGE LOW
Voltage received at actuator is below expected range
ACT OVER V
n/a n/a
ACTUATOR VOLTAGE HIGH
Voltage received at actuator is above expected range
ACT STALLED
n/a n/a
ACTUATOR STALLED
Actuator stopped before reaching commanded position
*Table 11 illustrates the complete hierarchy. your menu parameters may be different depending on your configuration.
LEGEND
LCD Liquid Crystal Display
MAT Mixed Air Temperature
OAT Outdoor Air Temperature
OCC Occupied
RAT Return Air Temperature
RTU Rooftop Unit
CHECKOUT TESTS
Use the Checkout menu (see Table 11) to test the damper operation
and any congured outputs. Only items that are congured are
shown in the Checkout menu.
NOTE: See User Interface for information about menu navigation
and use of the keypad.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the ▲
and ▼ buttons.
2. Press the button to select the item.
3. RUN? appears.
4. Press the button to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all desired parameters have been tested, press the
↑ (Menu up) button to end the test.
Checkout test can be performed at any time during the operation of
the system as a test that the system is operable.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to equipment
Be sure to allow enough time for compressor startup and
shutdown between checkout tests so that you do not short-cycle
the compressors.
!