9.2.3 E3(indoor fan speed out of control) diagnosis
Is the indoor fan motor connector and
The unit does not work normally
Turn off the unit, rotate the cross fan.
Disassemble the connection between fan
and motor, check if the bearing is normal.
If not, change the bearing. If yes, follow
Check the voltage between the red and
black wires of motor power input .Is it in
range of AC90-160V?
Shut off the power supply and turn on it 5s later