5.4 CompressorandInverterModuleProtectionControl
Thiscontrolprotectsthecompressorsfromabnormallyhighcurrentsandprotectstheinvertermodulesfromabnormally
hightemperatures.
Figure3‐5.4:Compressorcurrentprotectioncontrol

5.5 DisableCoolingControl
Whentheoutdoorambienttemperaturedropsbeloworequalto-15°C cooling mode is disabled to prevent low
compressionratioswhichcanresultininsufficientcompressorinternaloillubrication,andpreventhumidcompressedinlow
superheatofcompressorbottomconditions.Whentheoutdoorambienttemperaturerisesaboveorequalto-14°C,the
compressorentersre-startcontrol.
Figure3‐5.6:Disableheatingcontrol
Current≥Current
max
Current<Current
max
Normaloperation
Compressorcurrentprotection,errorcodeP3isdisplayed
Outdoorambienttemperature-15
o
C
Outdoorambienttemperature≥-14
o
C
Coolingoperation
Unitsstop