AtomBSeriesVRF50/60Hz
21
Part3‐Control
6 SpecialControl
6.1 OilReturnOperation
Inordertopreventcompressorsfromrunningoutofoil,theoilreturnoperationisconductedtorecoveroilthathasflowed
outofthecompressor(s)and intothepipingsystem.Thisoperationisperformedforallunits includingunits thatarein
standby.
Timingofoilreturnoperation:
Whentheinitialcumulativeoperatingtimereachesevery8hours.
Tables3-6.1and3-6.2showcomponentcontrolduringoilreturnoperationincoolingmode.
Table3‐6.1:Outdoorunitcomponentcontrolduringoilreturnoperationincoolingmode
Component
Wiringdiagram
label
28‐60model Controlfunctionsandstates
Invertercompressor COMP Fixedfrequency
DCfanmotor FAN
Normalcontrolascoolingoperation
Electronicexpansionvalve EEV1
Position300(steps)
Four-wayvalve ST1
Off
Table3‐6.2:Indoorunitcomponentcontrolduringoilreturnoperationincoolingmode
Component Unitstate Controlfunctionsandstates
Fan
Thermoon Remotecontrollersetting
Standby Remotecontrollersetting
Thermooff Off
Electronicexpansionvalve
Thermoon Normalcontrol
Standby 300(steps)
Thermooff 300(steps)
Tables3-6.3and3-6.4showcomponentcontrolduringoilreturnoperationinheatingmode.
Table3‐6.3:Outdoorunitcomponentcontrolduringoilreturnoperationinheatingmode
Component Wiringdiagramlabel 28‐60model Controlfunctionsandstates
Invertercompressor COMP Fixedfrequency
DCfanmotor FAN
Fan speed controlled according to
heatexchangertemperature(T3)and
outdoorambienttemperature(T4)
Electronicexpansionvalve EEV1
Position300(steps)
Four-wayvalve ST1
Off
Table3‐6.4:Indoorunitcomponentcontrolduringoilreturnoperationinheatingmode
Component Unitstate Controlfunctionsandstates
Fan
Thermoon Operateonsettingfanspeed(Preventcoldwindpriority)
Standby Operateonsettingfanspeed(Preventcoldwindpriority)
Thermooff Off
Electronicexpansionvalve
Thermoon Normalcontrol
Standby 480(steps)
Thermooff 480(steps)
NotePreventcoldwindIt’sonlyvalidinheatingoperation,andthiscontrolisprioritytoothercontrols(includingheatingoilreturnanddefrost),
Whichdeterminetheconversionbetweensettingfanspeedwithlowfanspeedandturnoffthefanaccordingtotheevaporatorcoiltemperature
T2.