Atom B Series VRF 50/60Hz
50
Midea
Atom B
Series
Service Manual
2.4 E2: Communication error between outdoor unit and indoor units (For all models)
2.4.1 Digital display output
E2
2.4.2 Description
Communication error between outdoor unit and indoor units.
The system stops running.
Error code is displayed on the outdoor unit PCB.
2.4.3 Trigger / recover condition
Trigger condition: Indoor units and the outdoor unit cannot communicate for 2 minutes after the system is powered on
for 20 minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
2.4.4 Possible causes
Communication wires between indoor and outdoor units did not connected properly.
Indoor unit power supply abnormal.
Loosened wiring within electric control box.
Interference from high voltage wires or other sources of electromagnetic radiation.
Communication wire too long.
Damaged main PCB or electric control box communication terminals block.
Communication wire break or poor contact for reasons (such as rat bite, or bond and connection).