Atom B Series VRF 50/60Hz
63
Part
6
-
Diagnosis and Troubleshooting
2.15 H7: The number of online indoor units have decreased/increased (For all models)
2.15.1 Digital display output
H7
2.15.2 Description
The number of online indoor units have decreased/increased.
The system stops running.
Error code is displayed on the unit with the error.
2.15.3 Trigger / recover condition
Trigger condition: The number of online indoor units have decreased/increased.
Recover condition: Number of indoor units detected is the same as first power on.
Reset method: Resume automatically.
2.15.4 Possible causes
Communication wire or power supply wire connection problem.
Indoor unit main control board damaged.
Outdoor unit main control board damaged.
2.15.5 Procedure
Waiting for 3 minutes to check whether
the fault would resume
There are some indoor units power off or
power on in the operation period
Inspect whether indoor unit address
repeat, clear and reset indoor unit’s
address to check whether fault cleared
Indoor unit address repeat
Inspect communication wire and power
supply wire whether exist loose or poor
connection problem
Connection wire installation problem
Power off outdoor unit and all indoor
units, and the repower on, turn on part
of indoor units to check whether outdoor
unit operate normally
Indoor unit main control board is fault
Outdoor unit main control board is fault