EasyManua.ls Logo

Midea ATOM MDV-V56WDHN1(AtB)

Midea ATOM MDV-V56WDHN1(AtB)
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Atom B Series VRF 50/60Hz
66
Midea
Atom B
Series
Service Manual
2.18 P1: Discharge pipe high pressure protection (For all models)
2.18.1 Digital display output
P1
2.18.2 Description
Discharge pipe high pressure protection.
The system stops running.
Error code is displayed on the outdoor unit PCB.
2.18.3 Trigger / recover condition
Trigger condition: Discharge pressure ≥ 4.4MPa.
Recover condition: Discharge pressure ≤ 3.2MPa.
Reset method: Resume automatically.
2.18.4 Possible causes
Pressure sensor/switch not connected properly or has malfunctioned.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Main PCB damaged.

Related product manuals