Atom B Series VRF 50/60Hz
77
Part
6
-
Diagnosis and Troubleshooting
2.21 P9: Poor reversing of four-way valve (For all models)
2.21.1 Digital display output
P9
2.21.2 Description
P9 indicates poor reversing of four-way valve.
The system stops running.
Error code is displayed on the outdoor unit PCB.
2.21.3 Trigger / recover condition
Trigger condition: Poor reversing of four-way valve.
Recover condition: Four-way valve recover to normal .
Reset method: Resume automatically.
2.21.4 Possible causes
Four-way valve is damaged.
Main PCB damaged.
2.21.5 Procedure
P8
Whether the four-way valve wires
connect good or not
Yes
Connect the four way
valve wires with the
port correctly
No
Main PCB damaged