Atom B Series VRF 50/60Hz
81
Part
6
-
Diagnosis and Troubleshooting
2.23.8 L8 / L9 troubleshooting
Compressor wiring is not properly
Reconnect the cables based on
wiring diagram
The resistance between 3 phases of
compressor is over 5Ω
The insulation resistance of
compressor is less than 100Ω
The compressor has less than 12
hours preheating before initial
operating
Ensure enough preheating time
Replace the compressor inverter
board, restart the unit and the error
is solved
Refer to P1 or P3 troubleshooting