8.3 Main Protection 
8.3.1 Three minutes delay at restart for 
compressor 
1 minute delay for the 1
st
 time stand-up and 3 
minutes delay for others. 
8.3.2 Temperature protection of compressor 
top 
The unit will stop working when the compressor 
top temp. protector cut off, and will restart after 
the compressor top temp. protector restart. 
8.3.3 Temperature protection of compressor 
discharge 
When the compressor discharge temp. is 
getting higher, the running frequency will be 
limited as below rules: 
---Compressor  discharge  temp.  T5>115 ℃
(239°F)  for  5s,  compressor  stops  and  restarts 
up till T5<90℃(194°F) 
---110<T5<115℃(239°F), decrease the 
frequency to the lower level every 2 minutes. 
---105(221°F)<T5<110℃(230°F),  keep  running 
at the current frequency. 
----T5<105℃(221°F), no limit for frequency. 
8.3.4 Fan speed is out of control 
When indoor fan speed keeps too low 
(300RPM) for certain time, the unit will stop and 
the LED will display the failure   
8.3.5 Inverter module protection 
The Inverter module has a protection function 
about current, voltage and temperature. If these 
protections happen, the corresponding code 
will display on indoor unit and the unit will stop 
working. 
8.3.6 Indoor fan delayed open function 
When the unit starts up, the louver will be active 
immediately and the indoor fan will open 7s 
later. 
If the unit runs in heating mode, the indoor fan 
will be also controlled by anti-cold wind 
function. 
8.3.7 Compressor preheating functions 
Preheating permitting condition: 
If T4(outdoor ambient temperature)<
3°C(37.4°F) and the machine connects to 
power supply newly or if T4<3°C(37.4°F) and 
compressor has stopped for over 3 hours, the 
compressor heating cable will work. 
Preheating mode: 
A weak current flow through the coil of 
compressor from the wiring terminal of the 
compressor, then the compressor is heated 
without operation. 
Preheating release condition: 
If T4>5°C(41°F) or the compressor starts 
running, the preheating function will stop. 
8.3.8 Sensor protection at open circuit and 
breaking disconnection. 
When there’s one temperature sensor in 
malfunction, the air conditioner will display error 
code and will not stop immediately, to avoid the 
case that the air conditioner is in urgent need.