Heating Capacity
MKG-600-C/ MKG-600-D
EWT ΔT
Indoor temperature (W.B.)
16 18 20 22
TH WF WPD TH WF WPD TH WF WPD TH WF WPD
°C °C kW m
3
/h kPa kW m
3
/h kPa kW m
3
/h kPa kW m
3
/h kPa
40
8 3.76
0.41 13.99 3.30 0.36 11.20 2.84
0.31 8.68 2.38
0.26 6.40
10 3.34 0.29 7.84 2.88 0.25 6.09 2.41 0.21 4.46 1.95 0.17 2.70
12 2.90 0.21 4.49 2.44 0.18 2.97 1.99 0.14 1.71 1.54 0.11 1.03
14 2.48 0.15 1.99 2.03 0.12 1.25 1.56 0.10 0.91 1.07 0.07 0.64
16 2.06 0.11 1.10 1.58 0.09 0.84 1.09 0.06 0.59 0.58 0.03 0.31
45
8 4.90
0.53 21.38 4.44 0.48 18.04 3.98
0.43 15.04 3.52
0.38 12.13
10 4.49 0.39 12.65 4.03 0.35 10.50 3.57 0.31 8.54 3.11 0.27 6.75
12 4.08 0.29 7.93 3.61 0.26 6.45 3.14 0.23 5.11 2.67 0.19 3.83
14
3.64
0.22 5.07 3.17 0.20 3.91 2.70
0.17 2.69 2.25
0.14 1.64
16 3.20 0.17 2.91 2.74 0.15 1.93 2.29 0.12 1.22 1.82 0.10 0.88
50
8 6.03
0.65 29.99 5.57 0.60 26.25 5.11
0.55 22.61 4.65
0.50 19.12
10
5.64
0.49 18.31 5.17 0.45 15.79 4.71
0.41 13.44 4.25
0.37 11.27
12 5.23 0.38 11.79 4.76 0.34 10.05 4.30 0.31 8.43 3.83 0.28 6.95
14
4.81
0.30 7.92 4.34 0.27 6.65 3.87
0.24 5.48 3.41
0.21 4.41
16
4.38
0.24 5.42 3.91 0.21 4.47 3.44
0.19 3.54 2.97
0.16 2.54
55
8 7.17 0.77 39.92 6.70 0.72 35.42 6.24 0.67 31.18 5.78 0.62 27.29
10
6.77
0.58 24.55 6.31 0.54 21.69 5.84
0.50 19.01 5.38
0.46 16.49
12 6.38 0.46 16.27 5.91 0.43 14.27 5.44 0.39 12.34 4.98 0.36 10.60
14 5.97 0.37 11.21 5.50 0.34 9.74 5.04 0.31 8.37 4.57 0.28 7.10
16
5.56
0.30 7.93 5.08 0.27 6.82 4.61
0.25 5.78 4.14
0.22 4.80
60
8 8.31 0.90 50.70 7.84 0.84 45.55 7.37 0.79 40.91 6.91 0.74 36.62
10
7.92
0.68 31.56 7.45 0.64 28.42 6.98
0.60 25.46 6.52
0.56 22.60
12 7.52 0.54 21.14 7.05 0.51 18.90 6.59 0.47 16.85 6.12 0.44 14.85
14 7.12 0.44 14.81 6.65 0.41 13.16 6.18 0.38 11.61 5.72 0.35 10.15
16
6.72
0.36 10.72 6.25 0.34 9.46 5.78
0.31 8.28 5.31
0.29 7.17
Abbreviations:
Δt: Temperature Difference. (℃)
TH: Total Heating Capacity. (kW) WF: Water Flow. (m
3
/h)
WPD: Water Pressure Drop. (kPa)