GD Midea Refrigerant Equipment Co. Ltd                                 Service manual for Electrolux split Series 
15 
2.7 AIR PURGING 
2.7.1 Air purging 
Air and moisture remaining in the refrigerant 
system have undesirable effects as indicated 
below. 
●  Pressure in the system rises. 
●  Operating current rises. 
●  Cooling (or heating if applicable) efficiency 
drops. 
●  Moisture in the refrigerant circuit may freeze 
and block capillary tubing. 
●  Water may lead to corrosion of parts in the 
refrigeration system. 
Therefore, the indoor unit and tubing between the 
indoor and outdoor unit must be leak tested and 
evacuated to remove any non-condensable 
substance and moisture from the system. 
2.7.2 Air purging with vacuum pump 
2.7.2.1 Preparation 
●  Check that each tube (both liquid and gas side 
tubes) between the indoor and outdoor units have 
been properly connected and all wiring for the test 
run has been completed. Remove the service 
valve caps from both the gas and the liquid side 
on the outdoor unit. Note that both the liquid and 
the gas side service valves on the outdoor unit are 
kept closed at this stage. 
2.7.2.2 Leak test 
●  Connect the manifold set (with pressure 
gauges) and dry nitrogen gas cylinder to this 
service port with charge hoses. 
 
 
 
 
 
 
●  Pressurizes the system to no more than 1MPa 
(Approx. 145psi) with dry nitrogen gas and close 
the cylinder valve when the gauge reading 
reaches 1MPa (Approx. 145psi). Next, test for 
leaks with liquid soap. 
 
Lo Hi
Indoor unit
Outdoor unit
Manifold set
Pressure
gauge
Charge hose
Nitrogen gas
cyli nder (in vertical
standing position)
 
 
 
 
 
 
 
 
●  Do a leak test of all joints of the tubing (both 
indoor and outdoor) and both gas and liquid side 
service valves. Bubbles indicate a leak. Be sure to 
wipe off the soap with a clean cloth.   
●  After the system is found to be free of leaks, 
relieve the nitrogen pressure by loosening the 
charge hose connector at the nitrogen 
cylinder. When the system pressure is 
reduced to normal, disconnect the hose from 
the cylinder. 
Gas leak check
 
1. Apply a soap water or a liquid neutral detergent 
CAUTION 
To avoid nitrogen entering the refrigerant   
system in a liquid state, the top of the cylinder   
must be higher than its bottom then you   
pressurise the system. Usually, the cylinder is   
used in a vertical standing position. 
CAUTION 
Be sure to use a manifold set for air purging. If it 
is not available, use a stop valve for this 
purpose. The "Hi" knob of the manifold valve 
must always be kept closed.