E1/EL01 – Comms Error
If all is ok with field cabling and wiring
Use your multimeter to measure the dc voltage between terminals S
& N (black tester S / red tester N)
Voltage should flucate between + and - values
If the voltage is fixed it is the indoor board at fault
If the voltage fluctuates but only with positive values it is the outdoor
board at fault
Check spade connections onto boards. If all is good, condemn the
applicable PCB