202004                                                                                                                                                                                                                      55
Procedure 4.3.4
E1     
     
   
The phase sequence of the 3-phase 
power supply
 
is incrorrect
1
 
Yes 
Exchange any two of the 3 phase wires
    No 
   
Some power supply terminals are loose
2
 
Yes 
Ensure all supply terminals are securely 
fastened 
    No 
   
The power supply is abnormal 
Yes 
Check the power supply equipment   
    No 
   
Replace outdoor unit main PCB     
Notes:   
1.  The A, B, C terminals of 3-phase power supply should match compressor phase sequence requirements. If the phase sequence is inverted, the compressor 
will operate inversely. If the wiring connection of each outdoor unit is in A, B, C phase sequence, and multiple units are connected, the current difference 
between C phase and  A, B phases  will be  very large as  the  power supply load of  each outdoor unit will be  on C phase. This can easily lead to tripped 
circuits and terminal wiring burnout. Therefore if multiple units are to be used, the phase sequence should be staggered, so that the current is distributed 
among the three phases equally.   
2.  Loose power supply terminals can cause the compressors to operate abnormally and compressor current to be very large. 
   