DM16-01.01.11-01en   Service manual 
Multi DC inverter R410A. Outdoor unit    35 
Over voltage or over low voltage protection  P1  ☆  2 
Too low ambient temperature protection  P3  ☆  4 
Error rotor position protection of compressor  P4  ☆  5 
Mode conflict  P5  ☆  6 
Low pressure protection of compressor  P6  ☆  7 
O (on)   X(off)  ☆(flash at 2Hz) 
 
 
11.2 Outdoor unit error code explanation: 
Display LED STATUS 
E0  Outdoor EEPROM malfunction 
E2  Indoor / outdoor units communication error 
E3  Communication malfunction between IPM board and outdoor main board 
E4  Open or short circuit of outdoor unit temperature sensor 
E5 Voltage protection 
E8  Outdoor fan speed has been out of control 
F1  No A Indoor unit coil outlet temperature sensor or connector of sensor is defective 
F2  No B Indoor unit coil outlet temperature sensor or connector of sensor is defective 
F3  No C Indoor unit coil outlet temperature sensor or connector of sensor is defective 
F4  No D Indoor unit coil outlet temperature sensor or connector of sensor is defective 
F5  No E Indoor unit coil outlet temperature sensor or connector of sensor is defective 
P1 
High pressure protection (ForM4OE-28HFN1-Q, M4OB-36HFN1-Q, M5OE-42HFN1-Q) 
P2  Low pressure protection (ForM4OE-28HFN1-Q, M4OB-36HFN1-Q, M5OE-42HFN1-Q) 
P3  Current protection of compressor 
P4  Temperature protection of compressor discharge 
P5  High temperature protection of condenser 
P6  IPM module protection 
LP  Low ambient temperature protection 
Note: Once these error codes display, they will disappear in at least 30 seconds if the unit come back to 
normal. (Except E2&E3)