Display running frequency, running state or malfunction code
No. of indoor units in good connection
Outdoor unit running mode code
Off:0,Fan only 1, Cooling:2, Heating:3, Forced cooling:4
The capacity unit is horse power. If the indoor unit is not connected, the digital
display tube will show: “――”
(9K:1HP,12K:1.2HP,18K:1.5HP)
A Indoor unit capacity demand code
Norm code*HP
(9K:1HP,12K:1.2HP,18K:1.5HP)
B Indoor unit capacity demand code
C Indoor unit capacity demand code
D Indoor unit capacity demand code
E Indoor unit capacity demand code
Outdoor unit amendatory capacity demand code
The frequency corresponding to the total indoor
units amendatory capacity demand
The frequency after the frequency limit
The frequency sending to compressor control
chip
A indoor unit evaporator outlet temp.(T
2B
A)
If the temp. is lower than -9 degree, the digital display tube will show “-9”.If the
temp. is higher than 70 degree, the digital display tube will show “70”. If the
indoor unit is not connected, the digital display tube will show: “――”
B indoor unit evaporator outlet temp.(T
2B
B)
C indoor unit evaporator outlet temp.(T
2B
C)
D indoor unit evaporator outlet temp.(T
2B
D)
E indoor unit evaporator outlet temp.(T
2B
E)
A indoor unit room temp.(T
1
A)
If the temp. is lower than 0 degree, the digital display tube will show “0”.If the
temp. is higher than 50 degree, the digital display tube will show “50”. If the
indoor unit is not connected, the digital display tube will show: “――”
B indoor unit room temp.(T
1
B)
C indoor unit room temp.(T
1
C)
D indoor unit room temp.(T
1
D)
E indoor unit room temp.(T
1
E)
A indoor unit evaporator temp.(T
2
A)
If the temp. is lower than -9 degree, the digital display tube will show “-9”.If the
temp. is higher than 70 degree, the digital display tube will show “70”. If the
indoor unit is not connected, the digital display tube will show: “――”
B indoor unit evaporator temp.(T
2
B)
C indoor unit evaporator temp.(T
2
C)
D indoor unit evaporator temp.(T
2
D)
E indoor unit evaporator temp.(T
2
E)
Outdoor ambient temp.(T4)
Compressor discharge temp.(Tp)
The display value is between 30~129 degree. If the temp. is lower than 30
degree, the digital display tube will show “30”.If the temp. is higher than 99
degree, the digital display tube will show single digit and tens digit. For
example, the digital display tube show “0.5”,it means the compressor
discharge temp. is 105 degree.)