9.4.2.7 E8(Outdoor fan speed has been out of control) diagnosis and solution(Only for DC fan motor
models).
Error Code
E8
Malfunction decision
conditions
When outdoor fan speed keeps too low (300RPM) or too high(2400RPM)
for certain time, the unit will stop and the LED will display the failure.
Supposed causes
Wiring mistake
Fan ass’y faulty
Fan motor faulty
PCB faulty
Trouble shooting:
Shut off the power supply
and turn it on 1 minute
later. Is it still displaying
the error code?
Shut off the power supply,
rotate the fan by hand.
Does it rotate properly?
The unit operates normally.
Find out the cause and
have it solved. For
example, check
whether the fan is
blocked or the bearing
is broken?
Check the wires of fan
motor. Are all the
connections good?
No
Yes
No
Correct the connections.No
Yes
Check whether the main PCB is
normal through index 2?
Yes
Yes
Check whether the fan
motor is normal through
index 1?
Yes
Replace the fan
motor
Replace the
main PCB.
The
malfunction is
solved?
No
No
If the
malfunction is
still existing,
replace the
main PCB
No