EasyManua.ls Logo

Midea M5OE-42HFN1-Q - Page 8

Midea M5OE-42HFN1-Q
57 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service manual DM16-01.01.11-01en
8 Multi DC inverter R410A. Outdoor unit
Outdoor Model M4OB-36HFN1-Q
Indoor unit combination Single Double Three Four
Power supply V-ph-Hz 220-240V- 50Hz, 1Ph
Cooling
Capacity Btu/h 7000-18000 14000-26000 21000-36000 36000
Input W 1250-1700 1650-2320 2150-3520 3505
Rated current A 5.4-7.4 7.2-10.1 9.3-15.3 15,2
EER W/W / / / 3,01
Heating
Capacity Btu/h 7000-20000 16000-29000 24000-38000 38000
Input W 1375-2440 2050-3340 2880-3360 3266
Rated current A 5.9-10.6 8.9-14.5 12.5-14.6 14,2
COP W/W / / / 3,41
Max. input consumption W 4600
Max. input current A 21.5
Compressor
Model ATF310D43UMT
Type ROTARY
Brand GMCC
Capacity Btu/h 32380
Input W 2600
Rated current(RLA) A 5,1
Locked rotor Amp(LRA) A -----
Thermal protector position INTERNAL
Capacitor μF -----
Refrigerant oil ml PQE(VG74)/1000
Outdoor fan
motor
New Model ZKFN-120-8-2
Model WZDK120-38G-W
Qty 1
Output W 120(Output)
Capacitor μF -----
Speed(Hi/Med/Lo) r/min 900
Outdoor coil
Number of rows 2
Tube pitch(a)* row pitch(b) mm 25.4x22
Fin spacing mm 1.3
Fin type Hydrophilic aluminium
Tube outside dia.and type mm Ф9.52, innergroove tube
Coil length * height * width mm 995x762x44
Number of circuits 4
Outdoor air flow m3/h 5500
Outdoor sound pressure level dB(A) 63.5
Throttle type Capillary+EXV
Outdoor unit
Dimension(WxDxH) mm 946x410x810
Packing(WxDxH) mm 1090x500x865
Net/Gross weight kg 70/75
Refrigerant
Type R410A
GWP 2088
Charged quantity Kg 3
Design pressure MPa 4.2/1.5
Refrigerant
piping
Liquid side/ Gas side mm(inch) 4 x Φ6.35/3x Φ9.52+1xΦ12.7(4x1/4"/3x3/8"+1x1/2")
Max. length for all rooms m 60
Max. length for one indoor unit m 30
Max. height difference
between indoor and outdoor
unit
OU higher than
IU
m 10
OU lower than
IU
m 15
Max. height difference between indoor units m 10
Ambient
temperature
Cooling -15-50
Heating -15-24
1.The above design and specifications are subject to change without prior notice for product improvement.
2.The values given in the table for the noise level reflect the levels in hemi-anechoic rooms.

Related product manuals