Safety 
Precautions
 Page 10
    cylinders. (No more than 80 % volume liquid charge).     i)  Do not exceed the maximum working 
    pressure of thecylinder, even temporarily.     j)  When the cylinders have been filled correctly and the 
    process completed, make sure that the cylinders and the equipment are removed from site promptly 
    and all isolation valves on the equipment are closed off.     k) Recovered refrigerant shall not be charged 
    into another refrigeration  system unless it has been cleaned and checked.
15.Labelling
    Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The 
    label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment 
    contains flammable refrigerant.
16.Recovery
    When removing refrigerant from a system, either for servicing or decommissioning, it is recommended 
    good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, 
    ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct 
    number of cylinders for holding the total system charge is available. All cylinders to be used are 
    designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the 
    recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off 
    valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before 
Before carrying out this procedure, it is essential that the technician is completely familiar with the 
equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. 
Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is 
required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before 
the task is commenced. 
14.Decommissioning
a) Become familiar with the equipment and its operation.    b) Isolate system electrically.    c) Before 
attempting the procedure ensure that: Mechanical handling equipment is available, if required, for 
handling refrigerant cylinders;All personal protective equipment is available and being used correctly; 
The recovery process is supervised at all times by a competent person; Recovery equipment and 
cylinders conform to the appropriate standards.    d) Pump down refrigerant system, if possible.    e) If a 
vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of  the
system.     f) Make sure that cylinder is situated on the scales before recovery takes place.    g) Start the 
recovery machine and operate in accordance with manufacturer's instructions.    h) Do not overfill 
13.Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed. Ensure
that contamination of different refrigerants does not occur when using charging equipment. Hoses or 
lines shall be as short as possible to minimise the amount of refrigerant contained in them. 
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it 
shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior 
to commissioning. A follow up leak test shall be carried out prior to leaving the site.
oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system 
with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and 
finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. 
When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable 
work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take 
place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 
ventilation available.