Electrical Control Function
114 Electrical Control System
-1.0
-2.0
-3.0
-4.0
0.0
T1-Ts+∆T
L
(H+-L)*0.4+L
(H+-L)*0.6+L
-5.0
-6.0
-6.5
H+
(H+-L)*0.8+L
(H+-L)*0.6+L
(H+-L)*0.2+L
For Compact cassette(12K)、A5(12K):
When the compressor is on, the indoor fan can be set to high, medium, low, auto and silent. And the
anti-cold wind function has the priority.
Auto fan action:
-3.5
T1-Ts-∆T
-4
High
Low
-5
Medium
-4.5
For other models:
When the compressor is on, the indoor fan can be set to high/medium/low/auto. And the anti-cold wind
function has the priority.
Auto fan action:
-2
T1-Ts-∆T
-3
High
Low
-5
Medium
-4