Troubleshooting 
Electrical Control System  127 
2.3 Outdoor unit malfunction 
18~36k 
Display Malfunction or Protection
E0  Outdoor EEPROM malfunction 
E2 
Indoor / outdoor units communication error 
E3 
Communication malfunction between IPM board and outdoor main board 
E4  Open or short circuit of T3 or T4 temperature sensor 
E5  Voltage protection of compressor 
E6  PFC module protection (For MOU-36HFN1-QRC4,MOU-36HFN1-QRC8) 
E8  Outdoor fan speed is out of control 
P0  Top temperature protection of compressor 
P1  High pressure protection (For 36k models) 
P2  Low pressure protection(For 36k models) 
P3  Current protection of compressor 
P4  Discharge temperature protection of compressor 
P5  High temperature protection of condenser 
P6  IPM module protection 
P7  High temperature protection of evaporator 
In low ambient cooling mode, the LED displays“LC”  or alternative displays between running frequency 
and “LC”(each displays 0.5s)