7. Fan Curves
ENC2
Static Pressure
Range In. WG (Pa)
Model
(K Btu/h)
Model 0 1 2 3 4
Model≤12
0.02
(5)
0.04
(10)
0.08
(20)
0.12
(30)
0.16
(40)
0-0.18
(0-45)
Model=18
0.04
(10)
0.10
(25)
0.14
(35)
0.18
(45)
0.22
(55)
0-0.28
(0-70)
18<Model≤24
0.04
(10)
0.10
(25)
0.16
(40)
0.22
(55)
0.28
(70)
0-0.40
(0-100)
24<Model≤60
0.08
(20)
0.14
(35)
0.20
(50)
0.26
(65)
0.32
(80)
0-0.40
(0-100)
Factory Setting