EasyManua.ls Logo

Midea MDV-252(8)W/D2RN1T(C)

Midea MDV-252(8)W/D2RN1T(C)
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V4+R VRF 50/60Hz
58 201608
Midea V4+R Series Service Manual
Procedure 4.5.4
E4 / E7
Temperature sensor connection on main
PCB is loose
1
Yes
Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed
2
Yes
Replace the sensor
No
Replace outdoor main PCB
Notes:
1. Outdoor ambient temperature sensor connection is port CN1 on the main PCB (labeled 32 in Figure 5-2.1 in Part 5, 2.2 Ports”). Compressor top
temperature sensor and discharge pipe temperature sensor connections are ports CN10 and CN11 on the main PCB (labeled 1 and 2, respectively, in Figure
5-2.1 in Part 5, 2.2 Ports).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensors resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 Layout of Functional Components and to Table 5-5.1 or 5-5.2 in Part 5, 5.1 Temperature
Sensor Resistance Characteristics”.

Table of Contents

Related product manuals