R410A DC Inverter VRF V4 Plus W Series 50Hz    MCAC-VTSM-2016-04 
14                                                                                                                                                                                          Selection Procedure 
2.  Unit Selection (Based on cooling load) 
2.1 Given condition   
  Design condition (Cooling: Indoor 20°C (WB), Outdoor 35°C (DB)) 
  Cooling load: 
  Power supply unit: Outdoor 380~415V-3Ph-50Hz, Indoor 220~240V-1Ph-50Hz. 
  Pipe length: 50m 
  Height difference: 30m 
2.2 Indoor unit selection 
Select the suitable capacity for condition of ‘Indoor 20°C (WB), Outdoor 35°C (DB)’ using indoor unit capacity 
table. The selected result is as follows. (Assuming the indoor unit type is duct) 
2.3 Outdoor unit selection 
a)  Assume the indoor unit and outdoor unit combination as follows 
  Calculate the  total  nominal capacity of indoor  units  in the  combination according to  the  above table: 
2.2×1+2.8×1+3.6×1+4.5×1+5.6× 1+7.1×1=25.8kW 
  Select outdoor unit: MDVS-280(10)W/DRN1 which has nominal cooling capacity: 28kW. 
  Calculate the proportion between  ①  and  ②: 258/280= 92% 
b)  Result : Because the proportion is within 50~130%, it is a Right selection. 
c)  Real function data with indoor unit combination 
  For the 92% combination, calculate the cooling capacity of outdoor unit (MDV-280(10)W/DRN1(B)). 
26.65KW  ←90% (Indoor temperature : WB 20°C, Outdoor temperature: DB 35°C) 
29.61KW  ←100%(Indoor temperature : WB 20°C, Outdoor temperature: DB 35°C) 
Then calculated the outdoor capacity in 92% combination index:   
Therefore: 26.65+ {(29.61-26.65)/ 10} ×2= 27.24;   
  Outdoor unit (MDVS-280(10)W/DRN1 cooling temperature: DB 35°C 
  Capacity modification coefficient with pipe length (50m) and height difference (30m): 0.958 
  Each indoor unit cooling capacity: 
MDV-D22T2: 27.24 × 22/258 × 0.958 = 2.22(kW) 
MDV-D28T2: 27.24 × 28/258 ×0.958 = 2.83 (kW) 
MDV-D36T2: 27.24 × 36/258 ×0.958 = 3.64 (kW) 
MDV-D45T2: 27.24 × 45/258 ×0.958 = 4.55 (kW) 
MDV-D56T2: 27.24 × 56/258 ×0.958 = 5.66 (kW)   
MDV-D71T2: 27.24 × 71/258 ×0.958 = 7.18 (kW) 
2.4  Conclusion 
Generally, we think this result is acceptable, so we can think we have accomplished the calculation. But if you 
think this result is not acceptable, you can repeat the above process. 
Remark: In this sample, we don’t consider the other capacity modification index and assume them are 1.0. 
For more details about the effect factor such as outside ambient/inside ambient DB/WD, please refer to the 
performance table of indoor and outdoor units.