EasyManua.ls Logo

Midea MFM-160N8R-1 - Pipe Length and Drop Height

Midea MFM-160N8R-1
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Page 9
2. Pipe Length and Drop Height
The length and elevation of connection pipe are shown in the table below. if the pipe length exceeds max pipe length,
additional refrigerant should be charged to ensure nominal cooling/heating capacity.
Capacity(Btu/h) Standard Length Max Pipe Length Max Elevation Additional Refrigerant
55k 5m (16.4ft) 75m(246ft) 30m(98.4ft)
24g/m (0.26oz/ft)
If oil flows back into the outdoor unit’s compressor, this might cause liquid compression or deterioration of oil return. Oil
traps in the rising gas pipe can prevent this.
-An oil trap should be installed every 6m(20ft) of vertical suction line riser (<36000Btu/h unit).
-An oil trap should be installed every 10m(32.8ft) of vertical suction line riser (36000Btu/h unit).
10m/32.8ft (≥36000Btu/h unit)
6m/20ft (36000Btu/h unit)
10m/32.8ft (≥36000Btu/h unit)
6m/20ft (36000Btu/h unit)
Indoor unit/
Outdoor unit
Indoor unit/
Outdoor unit

Table of Contents

Related product manuals