MCAC-ATSM-2014-01 R410A Mini Split Chiller 50Hz
39
E0: Water flow test malfunction
The water pump gets faulty.
Check whether the water system is blocked.
The ︳T
inlet water
– T
outlet water
︳>10℃.
Water flow switch gets faulty.
Check the water system and clean the filter.
Check the water pump, and repair or replace it
if necessary.
Check the water flow switch, and repair or
replace it if necessary.
There is air left in the water system.
Check whether the circulation water is insufficient.
Check and adjust the water system.