MCAC-2008-11 Air-cooled Modular Chiller
39
Water tank
kW is the unit for cooling capacity and L is the unit for G water flow in the formula counting the minimum
water flow.
Comfortable type air conditioner
G= cooling capacity×2.6L
Process cooling application conditioner
G= cooling capacity×7.4L
If the total water volume in the system is less than the required minimum volume, the additional water tank is
necessary in order to avoid the compressor On and Off frequently. The minimum size of the water tank is
calculated as: Size of additional water tank (L)= minimum water volume(L) – Actual water volume (L).
In certain occasion (especially in manufacture cooling process), for conforming the system water
content requirement, it’s necessary to mount a tank equipping with a cut-off baffle at the system to avoid
water short-circuit, Please see the following schemes: