Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
2
Content
1 General information ................................................................................ 3
2. Features ................................................................................................... 5
3. Specification ........................................................................................... 9
4 Dimension .............................................................................................. 21
5 Refrigeration system drawing .............................................................. 33
6. Piping diagram ...................................................................................... 36
7 Wiring diagrams..................................................................................... 42
8 Electric characteristics ......................................................................... 56
9 Capacity tables ...................................................................................... 58
10 Exploded view ...................................................................................... 74
11 Troubleshooting ................................................................................... 96
12 Installation .......................................................................................... 108
13 Commissioning .................................................................................. 132
14 Maintenance ....................................................................................... 135
15 Control system .................................................................................. 137
Appendix ................................................................................................. 174

Questions and Answers

  • V
    Vincent GardnerAug 20, 2025
    How to fix over high air discharge pressure in Midea MGCSL-F30W/RN1 (Cooling operation)?
    • C
      Carrie HernandezAug 20, 2025
      High air discharge pressure during cooling can stem from several issues. It could be due to air or non-condensing gas in the system, requiring you to discharge the gas and re-vacuum if needed. Dirty condenser fins or obstructions can also cause this, so clean the fins. Inspect the condenser fan for errors and ensure sufficient chilling air volume. Also, check if the ambient temperature is too high. Finally, if the refrigerant charging volume is excessive, discharge the extra refrigerant. If the air suction pressure is excessive high, refer to the section addressing that specific issue.
  • J
    Jason BaldwinAug 22, 2025
    What to do if my Midea MGCSL-F30W/RN1 compressor stops because of motor Overload?
    • C
      Carlos TorresAug 22, 2025
      If the compressor stops due to motor overload, the issue might be high air expelling and suction pressure (refer to those sections), voltage problems (ensure voltage isn't 20V above or below rated), a motor short circuit (check motor resistor connections), or an overload assembly error (replace the assembly).
  • M
    Mary ReedAug 25, 2025
    What causes a Midea MGCSL-F30W/RN1 compressor to stop due to freeze-proof protection (Cooling operation)?
    • S
      Steven GarciaAug 25, 2025
      The compressor might stop due to freeze-proof protection because of insufficient chilling water flow (check/repair the pump or flow control), gas in the water loop (discharge the air), or a thermal resistor error (replace it if confirmed).
  • C
    Christopher DayAug 27, 2025
    What causes over low air suction pressure in Midea MGCSL-F30W/RN1 Chiller (Cooling operation)?
    • J
      joseph94Aug 27, 2025
      Low air suction pressure can occur due to several reasons: insufficient water flow (adjust flow based on temperature difference), low inlet chilled-water temperature (check installation), refrigerant leaks or insufficient refrigerant (find and repair leaks or recharge), or scaling in the evaporator (descale).
  • K
    kcastilloAug 28, 2025
    Why is the air suction pressure over high in my Midea MGCSL-F30W/RN1 Chiller (Cooling operation)?
    • A
      andrewkleinAug 28, 2025
      High air suction pressure in cooling mode can result from overcharged refrigerant (discharge excess) or high inlet chilled-water temperature (check water pipeline insulation).
  • G
    gina87Aug 29, 2025
    Why is the air suction pressure over high in my Midea Chiller (Heating operation)?
    • N
      nancyjohnsonAug 30, 2025
      Excessive air suction pressure during heating can be due to overheated air at the air heat exchanger (check ambient temperature) or overcharging of refrigerant (discharge the excess).
  • S
    snyderrobertAug 31, 2025
    What causes a Midea MGCSL-F30W/RN1 Chiller compressor to stop due to Hi-pressure protection?
    • R
      Ruth WatsonAug 31, 2025
      If the compressor stops because of high-pressure protection, it could be due to over high air expelling pressure (refer to that section) or a faulty high-pressure switch (replace if defective).
  • B
    Brandon PriceSep 2, 2025
    How to fix over high air discharge pressure in Midea Chiller (Heating operation)?
    • S
      Sarah PerezSep 2, 2025
      High air discharge pressure during heating can be caused by insufficient water flow (adjust based on temperature difference), air or non-condensing gas in the system (discharge gas and re-vacuum if needed), scaling in the heat exchanger (descale), or high chilling water inlet temperature (check water temperature). If the air suction pressure is excessive high, refer to the section addressing that specific issue.
  • W
    William RogersSep 4, 2025
    What causes a Midea MGCSL-F30W/RN1 compressor to stop because of Lo-pressure protection?
    • M
      miguel58Sep 4, 2025
      If the compressor stops due to low-pressure protection, it could be a blocked filter in front or rear of the expanding valve (replace the filter), a faulty low-voltage switch (replace it), or excessive low air suction pressure (refer to that section).
  • M
    Michelle GarciaSep 6, 2025
    How to fix over low air discharge pressure in Midea MGCSL-F30W/RN1 (Cooling operation)?
    • J
      Jamie GuzmanSep 6, 2025
      Low air discharge pressure during cooling operation might be caused by a low surrounding temperature (measure the temperature) or a refrigerant leak or insufficient refrigerant (find the leak and recharge). If the suction pressure is low, refer to the “low suction pressure” section.

Summary

Features

Operational Range and Features

Details low ambient cooling, wide outlet water temp, and hydraulic module.

Specification

General Specifications

Overviews electrical, mechanical, and performance parameters for chiller units.

Wiring Diagrams

Chiller Wiring Diagrams by Module Size

Electrical wiring diagrams for various chiller module capacities.

Networking Communication Schematics by Module Size

Communication wiring for networked chiller systems across different module sizes.

Electric Characteristics

Electrical Characteristics Table

Details electrical properties like voltage, current, and power for various models.

Troubleshooting

Failure & Protection Codes by Module Type

Lists fault and protection codes for various chiller module types.

General Troubles and Solutions

Provides common troubleshooting steps and solutions for chiller system issues.

Installation

Unit Installation Procedures

Covers transportation, space, foundation, damping, and basic wiring precautions.

Water System Installation

Details pipeline, water quality, flow, tank, pump, and expansion tank installation.

Electrical Wiring and Connections

Covers power supply, wiring requirements, steps, and diagrams.

Commissioning

Preparation Steps

Outlines the necessary steps before starting the commissioning process.

Test Run Procedures

Details the procedure for conducting a trial run and performance checks.

Maintenance

General Maintenance and Component Care

Covers routine maintenance, scale removal, and replacement procedures.

Control System

Module PCB Layouts and Component Details

Visual guides and descriptions of PCBs and components for various chiller modules.

Wired Controller Operation and Installation

Covers wired controller functions, setup, and installation procedures.

Midea MGCSL-F30W/RN1 Specifications

General IconGeneral
BrandMidea
ModelMGCSL-F30W/RN1
CategoryChiller
LanguageEnglish

Related product manuals