MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
61
Heating:
Hot water outlet
temp.
Ambient temp.(℃)
-10 -6 -2 2 7 10 13
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
(℃) KW KW KW KW KW KW KW KW KW KW KW KW KW KW
39.00 19.89 6.13 24.86 6.97 29.25 7.74 32.50 8.42 35.33 8.86 39.57 9.39 45.50 10.14
41.00 19.22 6.26 24.06 7.11 28.34 7.90 31.52 8.59 34.30 9.04 38.34 9.58 44.02 10.35
42.00 18.67 6.38 23.39 7.26 27.58 8.06 30.72 8.76 33.46 9.22 37.34 9.78 42.79 10.56
43.00 18.22 6.52 22.86 7.40 26.98 8.23 30.08 8.94 32.80 9.41 36.54 9.98 41.81 10.77
44.00 17.86 6.65 22.44 7.55 26.53 8.39 29.61 9.12 32.32 9.60 35.94 10.18 41.04 10.99
45.00 17.60 6.78 22.14 7.71 26.21 8.57 29.28 9.31 32.00 9.80 35.52 10.39 40.49 11.22
46.00 17.26 6.85 21.74 7.79 25.76 8.65 28.81 9.40 31.52 9.90 34.92 10.49 39.74 11.33
47.00 16.75 6.99 21.12 7.94 25.06 8.82 28.06 9.59 30.73 10.10 33.99 10.70 38.61 11.56
48.00 16.09 7.20 20.31 8.18 24.13 9.09 27.05 9.88 29.66 10.40 32.74 11.02 37.13 11.90
49.00 15.21 7.49 19.23 8.51 22.87 9.45 25.67 10.27 28.17 10.81 31.05 11.46 35.15 12.38
50.00 14.23 7.86 18.02 8.93 21.45 9.92 24.10 10.79 26.48 11.36 29.13 12.04 32.92 13.00