MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Content 1
Content
Part 1 System outline ........................................................................................................................ 1
1. General outline .......................................................................................................................... 3
2. Pipe connection drawing .......................................................................................................... 26
3. Refrigeration system drawing ................................................................................................... 32
4. Wiring diagram ........................................................................................................................ 36
5 Networking communication wiring diagram .............................................................................. 42
6.Exploded view .......................................................................................................................... 48
Part 2 Capacity tables and control system ........................................................................................ 74
1. Capacity tables ......................................................................................................................... 75
2 Control system .......................................................................................................................... 89
Part 3 Trouble shooting ................................................................................................................. 138
1. Malfunction & protection codes ............................................................................................. 139
2 Troubles and Solutions ............................................................................................................ 145
3 Typical malfunction solutions .................................................................................................. 147
Part 4 Installation ......................................................................................................................... 156
1. Transportation and foundation installation............................................................................. 157
2. Water system installation ...................................................................................................... 165
3. Installation of water system pipeline ...................................................................................... 168
4. Wiring installation ................................................................................................................. 178
5. Trial run ................................................................................................................................. 182
Part 5 Maintenance ...................................................................................................................... 185
1. About maintenance ............................................................................................................... 186
2. Periodical check ..................................................................................................................... 188
Part 6 Wired controller.................................................................................................................. 190
1.1 KJRM-120D/BMK-E(Standard) .............................................................................................. 191
1.2 KJR-120A/MBTE(Optional) ................................................................................................... 200
Appendix ...................................................................................................................................... 209
Manufacture reserves the right to discontinue, or change at any time, specifications or designs without notices and
without incurring obligations

Table of Contents

Other manuals for Midea MGBT-F250W/RN1

Questions and Answers

  • B
    Brenda FranklinAug 20, 2025
    How to fix over high air discharge pressure in Midea MGBT-F250W/RN1 (Cooling operation)?
    • N
      Nicholas SawyerAug 20, 2025
      High air discharge pressure during cooling can stem from several issues. It could be due to air or non-condensing gas in the system, requiring you to discharge the gas and re-vacuum if needed. Dirty condenser fins or obstructions can also cause this, so clean the fins. Inspect the condenser fan for errors and ensure sufficient chilling air volume. Also, check if the ambient temperature is too high. Finally, if the refrigerant charging volume is excessive, discharge the extra refrigerant. If the air suction pressure is excessive high, refer to the section addressing that specific issue.
  • J
    Jessica WhiteAug 22, 2025
    What to do if my Midea Chiller compressor stops because of motor Overload?
    • B
      benjamin20Aug 22, 2025
      If the compressor stops due to motor overload, the issue might be high air expelling and suction pressure (refer to those sections), voltage problems (ensure voltage isn't 20V above or below rated), a motor short circuit (check motor resistor connections), or an overload assembly error (replace the assembly).
  • L
    lknightAug 25, 2025
    What causes a Midea MGBT-F250W/RN1 compressor to stop due to freeze-proof protection (Cooling operation)?
    • B
      Benjamin SmithAug 25, 2025
      The compressor might stop due to freeze-proof protection because of insufficient chilling water flow (check/repair the pump or flow control), gas in the water loop (discharge the air), or a thermal resistor error (replace it if confirmed).
  • L
    Lawrence ReedAug 26, 2025
    What causes over low air suction pressure in Midea MGBT-F250W/RN1 Chiller (Cooling operation)?
    • N
      Nathaniel JacksonAug 26, 2025
      Low air suction pressure can occur due to several reasons: insufficient water flow (adjust flow based on temperature difference), low inlet chilled-water temperature (check installation), refrigerant leaks or insufficient refrigerant (find and repair leaks or recharge), or scaling in the evaporator (descale).
  • L
    lbassAug 27, 2025
    Why is the air suction pressure over high in my Midea Chiller (Cooling operation)?
    • K
      Kiara MercadoAug 27, 2025
      High air suction pressure in cooling mode can result from overcharged refrigerant (discharge excess) or high inlet chilled-water temperature (check water pipeline insulation).
  • V
    victoriaroblesAug 29, 2025
    Why is the air suction pressure over high in my Midea MGBT-F250W/RN1 Chiller (Heating operation)?
    • D
      Deborah MoodyAug 29, 2025
      Excessive air suction pressure during heating can be due to overheated air at the air heat exchanger (check ambient temperature) or overcharging of refrigerant (discharge the excess).
  • D
    Danielle RiveraAug 31, 2025
    What causes a Midea MGBT-F250W/RN1 compressor to stop due to Hi-pressure protection?
    • B
      benjamin40Aug 31, 2025
      If the compressor stops because of high-pressure protection, it could be due to over high air expelling pressure (refer to that section) or a faulty high-pressure switch (replace if defective).
  • J
    John BeckSep 2, 2025
    How to fix over high air discharge pressure in Midea MGBT-F250W/RN1 Chiller (Heating operation)?
    • J
      Joseph CrawfordSep 2, 2025
      High air discharge pressure during heating can be caused by insufficient water flow (adjust based on temperature difference), air or non-condensing gas in the system (discharge gas and re-vacuum if needed), scaling in the heat exchanger (descale), or high chilling water inlet temperature (check water temperature). If the air suction pressure is excessive high, refer to the section addressing that specific issue.
  • K
    Kyle ClarkSep 4, 2025
    What causes a Midea MGBT-F250W/RN1 Chiller compressor to stop because of Lo-pressure protection?
    • C
      Crystal MorenoSep 4, 2025
      If the compressor stops due to low-pressure protection, it could be a blocked filter in front or rear of the expanding valve (replace the filter), a faulty low-voltage switch (replace it), or excessive low air suction pressure (refer to that section).
  • J
    Jason JonesSep 6, 2025
    How to fix over low air discharge pressure in Midea MGBT-F250W/RN1 Chiller (Cooling operation)?
    • J
      Joan GoodmanSep 6, 2025
      Low air discharge pressure during cooling operation might be caused by a low surrounding temperature (measure the temperature) or a refrigerant leak or insufficient refrigerant (find the leak and recharge). If the suction pressure is low, refer to the “low suction pressure” section.

Summary

Part 1 System outline

1. General outline

Provides overall system information, including product lists, specifications, features, and diagrams for various models.

Part 3 Trouble shooting

1. Malfunction & protection codes

Lists malfunction and protection codes with their corresponding trouble descriptions for various models.

2 Troubles and Solutions

Provides a table of common troubles, their possible reasons, and suggested solutions for troubleshooting.

3 Typical malfunction solutions

Offers troubleshooting flowcharts for common protection mechanisms like high/low pressure and temperature issues.

Part 4 Installation

5. Trial run

Details points for attention before, during, and after trial run, including check items and data.

Part 6 Wired controller

1.1 KJRM-120 D;BMK-E(Standard)

Details the wired controller's keys, operating instructions, functions, error handling, and installation.

1.2 KJR-120 A;MBTE(Optional)

Explains the wired controller's keys, operation procedures, logic, functions, and installation methods.

Midea MGBT-F250W/RN1 Specifications

General IconGeneral
Cooling Capacity250 kW
Compressor TypeScroll
Sound Pressure Level75 dB(A)
TypeAir Cooled Chiller
Power Supply380V/3Ph/50Hz