MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
63
Heating:
Hot water
outlet temp.
Ambient temp.(℃)
-10 -6 -2 2 7 10 13
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
(℃) Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
39.00 40.40 11.45 45.84 13.01 53.93 14.46 59.92 15.71 65.13 16.54 72.95 17.53 83.89 18.94
41.00 35.44 11.68 44.36 13.28 52.24 14.75 58.11 16.04 63.24 16.88 70.70 17.89 81.16 19.32
42.00 34.42 11.92 43.13 13.55 50.86 15.05 56.63 16.36 61.69 17.22 68.85 18.26 78.90 19.72
43.00 33.58 12.17 42.14 13.82 49.75 15.36 55.46 16.70 60.48 17.58 67.38 18.63 77.08 20.12
44.00 32.94 12.41 41.38 14.11 48.91 15.67 54.58 17.04 59.59 17.93 66.26 19.01 75.67 20.53
45.00 32.46 12.67 40.83 14.39 48.32 15.99 53.99 17.39 59.00 18.30 65.49 19.40 74.66 20.95
46.00 31.82 12.79 40.08 14.54 47.49 16.15 53.12 17.56 58.12 18.48 64.39 19.59 73.28 21.16
47.00 30.88 13.05 38.94 14.83 46.20 16.48 51.73 17.91 56.66 18.85 62.67 19.98 71.19 21.58
48.00 29.66 13.44 37.45 15.27 44.48 16.97 49.87 18.45 54.68 19.42 60.37 20.58 68.45 22.23
49.00 28.05 13.98 35.46 15.89 42.16 17.65 47.32 19.19 51.95 20.19 57.24 21.41 64.80 23.12
50.00 26.24 14.68 33.22 16.68 39.55 18.53 44.43 20.14 48.83 21.20 53.71 22.48 60.69 24.28