MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
69
Heating:
Hot water
outlet temp.
Ambient temp.(℃)
-10 -6 -2 2 7 10 13
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
(℃) kW kW kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
39.00 85.78 26.91 107.22 30.57 126.14 33.97 140.16 36.93 152.34 38.87 170.63 38.33 196.22 41.39
41.00 82.89 27.45 103.75 31.20 122.20 34.66 135.93 37.68 147.91 39.66 165.36 39.11 189.83 42.24
42.00 80.50 28.01 100.87 31.83 118.96 35.37 132.47 38.45 144.30 40.47 161.04 39.91 184.55 43.10
43.00 78.55 28.59 98.56 32.48 116.37 36.09 129.73 39.23 141.47 41.30 157.60 40.72 180.29 43.98
44.00 77.03 29.17 96.78 33.15 114.39 36.83 127.67 40.03 139.38 42.14 154.99 41.55 177.00 44.88
45.00 75.92 29.76 95.49 33.82 113.01 37.58 126.27 40.85 138.00 43.00 153.18 45.58 174.63 49.23
46.00 74.43 30.06 93.74 34.16 111.07 37.96 124.24 41.26 135.93 43.43 150.61 46.04 171.39 49.72
47.00 72.23 30.66 91.09 34.85 108.05 38.72 121.00 42.08 132.53 44.30 146.58 46.96 166.52 50.71
48.00 69.38 31.58 87.60 35.89 104.04 39.88 116.64 43.35 127.89 45.63 141.19 48.37 160.11 52.23
49.00 65.61 32.85 82.94 37.33 98.62 41.47 110.69 45.08 121.50 47.45 133.89 50.30 151.56 54.32
50.00 61.38 34.49 77.70 39.19 92.50 43.55 103.93 47.33 114.21 49.83 125.63 52.81 141.96 57.04