MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
71
Heating:
Hot water outlet
temp.
Ambient temp.(℃)
-10 -6 -2 2 7 10 13
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
(℃) Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
39.00 124.31 38.17 155.39 43.37 182.81 48.19 203.13 52.38 220.79 55.14 247.28 58.45 284.38 63.12
41.00 120.14 38.95 150.36 44.26 177.10 49.18 197.00 53.45 214.36 56.26 239.65 59.64 275.12 64.41
42.00 116.66 39.74 146.19 45.16 172.40 50.18 191.98 54.54 209.13 57.41 233.39 60.86 267.46 65.73
43.00 113.85 40.55 142.84 46.08 168.65 51.20 188.01 55.66 205.03 58.58 228.40 62.10 261.29 67.07
44.00 111.64 41.38 140.26 47.02 165.79 52.25 185.03 56.79 202.00 59.78 224.62 63.37 256.52 68.44
45.00 110.03 42.22 138.40 47.98 163.79 53.31 183.00 57.95 200.00 61.00 222.00 64.66 253.08 69.83
46.00 107.87 42.65 135.86 48.46 160.97 53.85 180.06 58.53 197.00 61.61 218.28 65.31 248.40 70.53
47.00 104.69 43.50 132.01 49.43 156.60 54.92 175.36 59.70 192.08 61.81 212.43 66.61 241.33 71.94
48.00 100.55 44.80 126.96 50.91 150.78 56.57 169.04 61.49 185.35 63.67 204.63 68.61 232.05 74.10
49.00 95.08 46.60 120.20 52.95 142.93 58.83 160.41 63.95 176.08 66.21 194.05 71.36 219.66 77.06
50.00 88.96 48.93 112.61 55.60 134.05 61.78 150.62 67.15 165.52 69.52 182.07 74.92 205.74 80.92