MCAC-TSM-2008-02 Outdoor units
Outdoor units 35
MGC-F14W/SN1
Ta.
U.R.87%
Tw 35 40 45 50
Pt 10.4 10.5 10.6 -
Pa 4.0 4.4 4.9 -
Pat 4.5 4.9 5.4 -
Qc 1.9 1.9 1.9 -
-5
Pc 15.2 15.1 15.0 -
Pt 13.1 13.0 13.0 12.9
Pa 4.0 4.4 4.9 5.4
Pat 4.5 4.9 5.4 5.9
Qc 2.3 2.3 2.3 2.3
0
Pc 21.1 21.1 21.0 20.9
Pt 16.2 16.2 16.1 16.0
Pa 4.1 4.5 5.0 5.5
Pat 4.6 5.0 5.5 6.0
Qc 2.8 2.8 2.8 2.8
7
Pc 31.2 31.1 31.0 31.0
Pt 17.6 17.5 17.4 17.4
Pa 17.6 17.5 17.4 17.4
Pat 17.6 17.5 17.4 17.4
Qc 3.1 3.1 3.1 3.1
10
Pc 36.4 36.2 36.0 35.9
Pt 19.8 19.7 19.6 19.4
Pa 4.3 4.5 5.2 5.7
Pat 4.8 5.0 5.7 6.2
Qc 3.5 3.5 3.5 3.5
15
Pc 45.4 45.2 45.0 44.9
Note:
Ta: outside air temperature (°C)
Tw : evaporator water outlet temperature (°C)
Pt: heating capacity (kW)
Pa: compressor power input (kW)
Pat: total power input (kW)
Qc: condenser water flow (m3/h)
ΔPc: evaporator pressure drop (kPa)