M thermal Mono
80 200204
Midea M thermal Mono Service Manual
Procedure
Discharge pipe temperature sensor
connection on refrigerant system main
PCB is loose
1
Ensure the temperature sensor is
connected properly
Backup electric heater water outlet
temperature sensor connection,
domestic hot water tank temperature
sensor connection or water side heat
exchanger water outlet temperature
sensor connection on hydronic system
main PCB is loose
2
Ensure the temperature sensor is
connected properly
Temperature sensor has short-circuited
or failed
3
High pressure switch connection or
pressure sensor connection on
refrigerant system main PCB is loose
4
Ensure the pressure switch is connected
properly
Pressure sensor has short-circuited or
failed
5
Replace the pressure sensor
The high pressure side is blocked, caused
by crushed or bent pipe or blocked EXV
4
Inspect the system and fix the error
The condenser heat exchange is poor in
heating mode
5
Inspect the system and fix the error
The water flow rate is not sufficient in
cooling mode
6
Inspect the water system and fix the
error