EasyManuals Logo

Midea MHC-V16W/D2N8-B User Manual

Midea MHC-V16W/D2N8-B
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
M thermal Mono
70 200204
Midea M thermal Mono Service Manual
4.13 H7 Troubleshooting
Digital display output
Description
Abnormal main circuit voltage.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Power supply voltage not within ±10% of rated voltage or a phase is missing.
Outdoor unit powered on immediately after being powered off.
Loosened wiring within electric control box.
High voltage circuit error.
Main PCB damaged.
Midea CAC Confidential

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MHC-V16W/D2N8-B and is the answer not in the manual?

Midea MHC-V16W/D2N8-B Specifications

General IconGeneral
BrandMidea
ModelMHC-V16W/D2N8-B
CategoryAir Conditioner
LanguageEnglish

Related product manuals