M thermal Mono         
102    200204 
Midea M thermal Mono Service Manual 
4.23 Pb Troubleshooting 
 Digital display output 
 
 Description 
  Water side heat exchanger anti-freeze protection. 
  M thermal Mono stops running. 
  Error  code  is  displayed  on  refrigerant  system  main  control  board  for  refrigerant  system  and  ANTI.FREEZE  icon  is 
displayed on user interface. 
 
 Possible causes 
  Normal system protection. 
  Temperature sensor not connected properly or has malfunctioned. 
  Hydronic system main PCB damaged. 
 
 Procedure 
 
Outdoor ambient temperature is lower 
than 4°C   
Normal system protection. The system 
will resume automatically
1
 
Water side heat exchanger water outlet 
temperature sensor, water inlet 
temperature sensor or backup electric 
heater outlet water temperature sensor 
loose
2
 
Ensure the temperature sensor is 
connected properly 
Water side heat exchanger water outlet 
temperature sensor, water inlet 
temperature sensor or backup electric 
heater outlet water temperature sensor 
has short-circuited or failed
3
 
Replace the temperature sensor 
 
Notes:   
1.  Refer to Part 3, 5.7 “Water Side Heat Exchanger Anti-freeze Protection Control”. 
2.  Backup electric heater water outlet temperature sensor, water side heat exchanger water inlet temperature sensor and water side heat exchanger water 
outlet temperature sensor connections are port CN6 on the hydronic system main PCB (labeled 8 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic 
System”). 
3.  Measure  sensor  resistance. If the  resistance is  too low,  the  sensor has  short-circuited.  If  the resistance  is  not  consistent  with  the  sensor’s  resistance 
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 4-5.3 in Part 4, 5.1 “Temperature Sensor 
Resistance Characteristics”.