4.5 E3, E4, H2, H3, Ed, HA, H5, H9 Troubleshooting 
 Digital display output 
   
   
   
   
   
 
 
 Description 
  E3 indicates a backup electric heater water outlet temperature sensor error. 
  E4 indicates a domestic hot water tank temperature sensor error. 
  H2 indicates a water side heat exchanger refrigerant outlet (liquid pipe) temperature sensor error. 
  H3 indicates a water side heat exchanger refrigerant inlet (gas pipe) temperature sensor error. 
  Ed indicates a water side heat exchanger water inlet temperature sensor error. 
  HA indicates a water side heat exchanger water outlet temperature sensor error. 
  H5 indicates a room temperature sensor error. 
  H9 indicates a zone 2 water outlet temperature sensor error. 
  Eb indicates solar panel temperature sensor error 
  E7 indicates balance tank upper temperature sensor error 
  EC indicates balance tank nether temperature sensor error 
  M thermal Mono stops running. 
  Error code is displayed on hydronic system main control board for refrigerant system and user interface. 
 
 Possible causes 
  Temperature sensor not connected properly or has malfunctioned. 
  Damaged hydronic system main PCB.