3 Error Code Table 
Table 4-3.1: Error code table
 
Error code  Content 
bH  PED PCB fault 
C7  High temp. protection of inverter module 
E0  Water flow fault (E8 displayed 3 times) 
E1  Phase loss or neutral wire and live wire are connected reversely (only for three phase unit) 
E2  Communication fault between controller and main control board of hydraulic module 
E3  Final outlet water temp. sensor (T1) fault. 
E4  Water tank temp. sensor (T5) fault. 
E5  The condenser outlet refrigerant temperature sensor (T3) fault 
E6  The ambient temperature sensor (T4) fault. 
E7  The balance tank up temp. sensor (Tbt1 ) fault. 
E8  Water flow fault. 
E9  Compressor suction temp. sensor (Th) fault. 
EA  Compressor discharge temp. sensor (Tp) fault 
Eb  Solar panel temp.sensor (Tsolar) fault. 
Ec  The balance tank low temp.sensor(Tbt2) fault 
Ed  The plate exchanger water inlet temp. sensor (Tw_in) fault. 
EE.  The main control board of hydraulic module EEPROM fault. 
F1  DC bus low voltage protection 
H0 
Communication  fault  between  main  control  board  of  h
ydraulic  module  and  main  control  board  PCB  B(Main  control 
board of unit) 
H1 
Communication  fault  between  inverter  module  PCB  A(Inverter  module)  and  main  control  board  PCB  B(Main  control 
board of unit) 
H2  The plate exchanger refrigerant outlet (liquid pipe) temp. sensor (T2) fault. 
H3  The plate exchanger refrigerant outlet (gas pipe) temp. sensor (T2B) fault. 
H4  Three times P6 protection 
H5  Room temp.sensor (Ta) fault 
H6  DC fan motor fault. 
H7  Main circuit voltage protection fault 
H8  Pressure sensor fault. 
H9  Zone 2 water flow temp. sensor (Tw2) fault.   
HA  The plate heat exchanger water outlet temperature sensor (Tw_out) fault. 
Hb 
Three times  PP   protection and Tw_out 7  
Hd  Communication fault between master unit and slave unit (in parallel) 
HE  Communication fault between indoor unit and Ta / room thermostart transfer PCB. 
HF  Inverter module board EE PROM fault 
HH  H6 displayed 10 times in 120 minutes. 
HP 
Low pressure protection  Pe<0.6   occured 3 times in 1 hour in cooling mode 
P0  Low pressure protection 
P1  High pressure protection 
P3  Compressor overcurrent protection 
 
Table 4-3.1: Error code table (continued) 
P4  Compressor discharge temp. too high protection 