M thermal Mono
44    202008 
Midea M thermal Mono 
Procedure 4.5.4
E3 / E4 / H
2 / H3 / Ed / HA / H5 / H9/ Eb   
/ E7 / EC 
   
     
   
Temperature sensor connection on 
hydronic system main PCB is loose
1
 
Yes 
Ensure the sensor is connected properly
    No 
   
Temperature sensor has short-circuited 
or failed
2
 
Yes 
Replace the sensor 
    No 
   
Replace hydronic system main PCB       
Notes:   
1.  Final water outlet temperature sensor,
 
water side heat exchanger refrigerant inlet (liquid pipe) temperature sensor, water side heat exchanger refrigerant 
outlet (gas pipe) temperature sensor, water side heat exchanger water inlet temperature sensor and water side heat exchanger water outlet temperature 
sensor connections are port CN6 on the hydronic system main PCB (labeled 10 in Figure 4-2.1).
 
Domestic hot water tank temperature sensor connection is 
port  CN13  on  the  hydronic  system  main  PCB  (labeled  13  in  Figure  4-2.1).  Circuit  2  water  outlet  temperature  sensor  connection  is  port  CN15  on  the 
hydronic system main PCB (labeled 14 in Figure 4-2.1). Room temperature sensor connection is port CN11 on the hydronic system main PCB (labeled 24 in 
Figure 4-2.1). Solar panel temperature sensor connection is port CN18 on the hydronic system main PCB (labeled 15 in Figure 4-2.1). Balance tank upper 
temperature  sensor  connection  is  port  CN24  on  the  hydronic  system  main  PCB  (labeled  11  in  Figure  4-2.1)  Balance  tank  nether  temperature  sensor 
connection is port CN16 on the hydronic system main PCB (labeled 12 in Figure 4-2.1) 
2. Set  a  multi-meter to  buzzer  mode  and  test any  two  terminals of  sensor.  If  the  resistance  is  too low,  the  buzzer  sounds,  which  means  the  sensor  has 
short-circuited. If the resistance is not consistent with the sensor s resistance characteristics table, the sensor has failed. Refer to Table 4-5.1 or 4-5.3. 
 
Midea CAC