L0 troubleshooting 4.20.6
Situation 1: L0 error appears immediately after the outdoor unit is powered-on 
L0     
     
   
Communication wire between refrigerant 
system main control board for refrigerant 
systemnd inverter module (4 pins) not 
connected properly
1
 
Yes 
Ensure communication wire is connected 
properly 
    No 
   
Inverter module is damaged
2
 
Yes   
    No 
   
Voltage between pins F0 and GND of 
communication port for connection to 
inverter module on the refrigerant 
system main PCB is too low
3
 
Yes 
Replace the inverter module
4
 
Notes:   
1.  The communication port between refrigerant system main control board for refrigerant system inverter module is port CN36 on refrigerant system main 
control board for refrigerant system port CN8 on inverter module.   
2.  Measure the resistance between each of U, V and W and each of P and N on the inverter module. All the resistances should be infinite. If any of them are 
not infinite, the inverter module is damaged and should be replaced. 
 
3.  The normal voltage between F0 and GND is 5V. Refer to Figure 4-4.2.
 
4.  When replacing an inverter module, a layer of thermally conductive silica gel should be painted on the IPM module (on the reverse side of the inverter 
module PCB). Refer to Figure 4-4.3.
 
 
Figure 4-4.2: F0 and GND voltage on IC28-1 F0 IC28-4 GND
 
    Vnormal = 5V
 
 
Figure 4-4.3: Replacing an inverter module
 
 
 
 
 
 
IPM 
  IC28-1 F0  
IC28-4 GND
 