L4 troubleshooting(the same as L1/L2)
Situation 1: L4 error appears immediately after the outdoor unit is powered-on
Condition 2: L4 error appears after the compressor has been running for a period of time and the compressor speed is
over 60rps
Compressor is over-current
2
Notes:
1. Re-start the unit, use clip-on ammeter to measure the compressor current, if the current is normal indicates the compressor is failed, if the current is
abnormal indicates the inverter PCB is failed..
L5/L8/L9 troubleshooting
The wire is not connected properly
Ensure wire is connected properly
Inverter module PCB has malfunctioned
Replace inverter module PCB