4.24 Pd Troubleshooting
Digital display output
Description
High temperature protection of air side heat exchanger refrigerant outlet in cooling mode. When the air side heat
exchanger refrigerant outlet temperature is higher than 61°C for more than 3 seconds, the system displays Pd
protection and M thermal Mono stops running. When the air side heat exchanger refrigerant outlet temperature
returns drops below 55°C, Pd is removed and normal operation resumes.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Poor condenser heat exchange.
Fan motor damaged.
Hydronic system main PCB damaged.